Illuminance study: how to calculate the light in a space

How much light does a room need? The answer is not on a bulb, it is calculated. Lux, uniformity, standards and simulation: how an illuminance study works.
Architecture studio with a screen showing a lighting simulation, printed plans and a lux meter on the desk

Summary

“How much light does this room need?” The question sounds simple, yet the answer is not printed on a lamp’s packaging, nor does it lie in the number of spotlights. It is calculated. That is the purpose of an illuminance study: determining, before the works, how much light will actually reach the useful surfaces, and checking that it is well distributed.

Lumens, lux, candelas: don’t mix them up

The most common confusion comes from the units. They measure three different things:

UnitWhat it measuresPractical example
Lumen (lm)The total amount of light emitted by a sourceAn 800 lm lamp, whatever the direction
Candela (cd)Luminous intensity in a given directionA narrow-beam spotlight concentrates its lumens, so many candelas along its axis
Lux (lx)The light received on a surface, in lumens per m²500 lux measured on a desk

An illuminance study works in lux, because that is what the eye perceives on the worktop, the counter or the floor. Two fittings with the same luminous flux in lumens can produce very different illuminance depending on their optics, height and orientation.

Screen showing a photometric simulation of an office floor with false-colour light levels

What the study actually calculates

  • Average illuminance (Em) on each useful area: workstations, tables, sales areas, circulation.
  • Uniformity (Uo), the ratio between minimum and average illuminance. Uniformity that is too low creates shadowy areas that tire the eyes.
  • Glare, expressed by the UGR index, which we explain in our article on UGR standards.
  • The maintenance factor : fittings lose output with age and dust. The calculation accounts for this so that illuminance stays sufficient over time, not just on installation day.

Reference values from EN 12464-1

For workplaces, the European standard EN 12464-1 sets minimum values by activity. Some common reference values:

SpaceMaintained illuminanceUniformity (Uo)Maximum UGRMinimum CRI
Office, screen work500 lux0.601980
Meeting room500 lux0.601980
Sales area300 lux0.402280
Checkout area500 lux0.601980
Corridors, circulation100 lux0.402840

These are minimums. A shop that wants to stand out often lights its products well beyond them, while an atmospheric venue such as a restaurant plays instead on lower, more contrasted levels. For shops, our article on the optimum lighting level for a commercial space goes further.

Photometric simulation: see it before installing

On larger projects, the calculation is done in simulation software such as DIALux or Relux. The principle:

  1. The room is modelled in 3D, with its dimensions, openings and surface colours, since a dark wall absorbs far more light than a white one.
  2. The photometric files of the fittings under consideration are imported, in LDT or IES format, supplied by manufacturers. They describe precisely how each fitting distributes its light.
  3. The software calculates illuminance at every point, uniformity and glare, and produces isolux curves and visual renderings.
  4. Layout, models or outputs are adjusted until the target is met, without installing a single fitting.

Simulation avoids two costly pitfalls: under-lighting, which has to be corrected afterwards, and over-lighting, which wastes energy and causes discomfort.

What the calculation does not do

Compliant illuminance does not guarantee beautiful light. An office can show a perfectly uniform 500 lux and still feel cold and flat. The calculation is a verification tool, not an intention. That is why an illuminance study fits into a broader approach that also considers atmosphere, colour temperature, accent lighting and the architecture of the space.

Digital lux meter measuring illuminance on a desk under a linear LED luminaire

Conclusion

An illuminance study gives a measured answer to a question too often handled by instinct: how much light, and where. It secures a project, avoids costly corrections and ensures professional spaces comply with standards. To go beyond the calculation and design the whole lighting atmosphere, our custom lighting design study includes these checks, whether for offices, a retail space or a hotel.

Our lighting consultants: discover their projects

A bright project?

We’re here to support you every step of the way, from concept to completion.

Our areas of expertise in lighting

More Technical advice to discover

  • Eclairage commercial

    Calculating the optimum lighting level for a commercial space

    Find out more

    Expertise Calculating the optimum lighting level for a commercial space
  • Eclairage magasin hyper

    Why and how can you replace your old TL tubes with LEDs?

    Replace your TL fluorescent tubes with LED tubes and make significant energy savings while improving lighting quality. Find out more about the benefits, compatibility and best practice for a successful conversion.

    Find out more

    Expertise Why and how can you replace your old TL tubes with LEDs?
  • illu-rodalight-tarifs-eclairage-5

    How do you light dark offices properly?

    More and more companies are opting for open-plan offices. They often cover a large surface area and are more likely to benefit from outside light. It is therefore necessary to provide a lighting solution so that everyone can concentrate in the same way.

    Find out more

    Expertise How do you light dark offices properly?
Let's chat!